Ingecon SUN 110TL M9 Manual
INGECON® SUN 110TL M9
Overview
The INGECON® SUN 110TL M9 is a three-phase PV inverter designed for industrial self-consumption systems. It features nine independent Maximum Power Point Trackers (MPPT) and a DC/AC power conversion stage to optimize energy from the PV modules, even in challenging conditions such as scattered clouds and partial shading.
Key Features
- Maximum Efficiency: 98.2% with nine independent MPPT inputs.
- Plug & Play Technology: Fast and easy installation with country-specific configuration via App or PC.
- Rugged Design: Designed for indoor and outdoor applications (IP66).
- Ease of Maintenance: Internal datalogger, remote and on-site control, and LED status indicators.
- Software Included: INGECON® SUN Monitor and iSun Monitor for monitoring and recording inverter data over the internet.
- Communications: Ethernet and Wi-Fi as standard.
- Warranty: Standard 5-year warranty, extendable up to 25 years.
Main Features
- EMS inside.
- Multi-MPPT system.
- 98.2% maximum efficiency.
- Digital inputs.
- Ethernet and Wi-Fi communications supplied as standard.
- Remote configuration and upgrade.
- Software INGECON® SUN Monitor for PV plant monitoring.
- LED Status.
- Easy maintenance.
- Plug & Play technology.
- Suitable for indoor and outdoor installations (IP66).
- High temperature performance.
- Compact design.
- Configurable language, rated voltage, and country code via App.
- Compatible with high power modules (500W-600W+).
Protections
- Reverse polarity protection.
- Short circuits and overloads at the output.
- Anti-islanding with automatic disconnection.
- Insulation faults.
- Input and output overvoltages with type II surge arresters.
Optional Accessories
- Self-consumption kit.
Benefits
- Greater performance thanks to the multi MPPT system.
- Easy maintenance.
- Higher inverter life expectancy.
- Waterproof and dustproof (IP66).
- Anti-corrosion with C4 protection class.
All models feature DC and AC surge arresters type II and an integrated DC switch.
Technical Specifications
Specification | 110TL M9 |
---|---|
Input (DC) | |
Recommended PV array power range | 113.3 - 165 kWp |
Voltage range MPPT | 200 - 1,000 V |
Maximum voltage | 1,100 V |
Rated input voltage | 600 V |
Start input voltage / Min. operating voltage | 250 V / 200 V |
Max. Short circuit current | 3x50A + 6x45A |
Maximum current | 3x40A + 6x32A |
Inputs with PV connectors | 18 (9x2) |
Number of MPPTs | 9 |
Output (AC) | |
Rated power | 110 kW |
Max. apparent power (1) | 123 kVA |
Max. active power (PF = 1) (1) | 121 kW |
Max. output current | 187 A |
Rated voltage | 400 V |
Voltage range (2) | 322 V - 520 V (Adjustable) |
Frequency | 50 / 60 Hz |
Type of grid | TT / TN / IT |
Power Factor adjustable | Yes, 0 - 1 (leading / lagging) |
Efficiency | |
Maximum efficiency | 98.2% |
Euroefficiency | 97.8% |
General Information | |
Refrigeration system | Forced ventilation |
Consumption at night | < 10 W |
Ambient temperature | -25°C to 60°C |
Relative humidity (non-condensing) | 0 - 100% |
Protection class | IP66 |
Marking | CE |
Acoustic emissions | < 65 dB |
Max. Operating altitude | 4,000 m |
EMC and security standards | EN 61000-6-2, EN 61000-6-4, EN 62109-1, EN 62109-2 |
Grid connection standards | IEC 61727:2004, IEC 62116:2014, EN 50549-1:2019, EN 50549-2:2019, UNE 217002:2020, UNE 217001:2020, NTS SEPE 2.1 type B, CEI 0-21 v1 November 2022 (including Allegato B), CEI 0-16 v1 November 2022 (including Allegato N), VDE-AR-N 4105:2018, DIN VDE V 0124-100/06.20 |
Integrated Elements | |
DC switch | Yes |
Anti-islanding protection | Yes |
AC overcurrent protection | Yes |
AC short-circuit protection | Yes |
DC reverse connection | Yes |
DC & AC surge arresters, type II | Yes |
Insulation detection | Yes |
Leakage current protection | Yes |
PV String monitoring | Yes |
Night load consumption monitoring | Yes |
Dimensions and Weight
-
110TL M9:
- Dimensions: 936 x 678 x 365 mm
- Weight: 92 kg
Notes
- In Spain, the maximum active power will be the same as the rated power.
- The range of output voltage and frequency may vary depending upon different grid codes.
For further information:
- Website: Ingeteam