PVS800-57B Manual
Central Inverter PVS800-57B
Key Features:
- Power Capacity: Nominal ratings range from 1645 kW to 1732 kW.
- High Efficiency: Maximum efficiency of 98.5%, Euro efficiency of up to 98.4%.
- Design: Compact and modular for ease of installation and maintenance.
- Cooling System: Self-contained, low-maintenance cooling system.
- Protection: Extensive DC and AC side protection, including low voltage ride through (LVRT) and reactive power control.
- Grid Support: Advanced grid support features for active/reactive power output control and grid stability.
- Communication: Complete range of industrial data communication options, including remote monitoring.
Technical Specifications:
-
Input (DC):
- Maximum input power (PPV, max): 2468 kWp to 2598 kWp.
- DC voltage range, mpp (UDC, mpp): 550 to 850 V to 580 to 850 V.
- Maximum DC voltage (Umax (DC)): 1000 V.
- Maximum DC current (Imax (DC)): 3700 A.
- Number of protected DC inputs: 16 to 24.
-
Output (AC):
- Nominal power (PN(AC)): 1645 kW to 1732 kW.
- Maximum output power: 1975 kW to 2078 kW.
- Power at cosφ = 0.95: 1562 kW to 1645 kW.
- Nominal AC current (IN(AC)): 2500 A.
- Nominal output voltage (UN(AC)): 380 V to 400 V.
- Output frequency: 50/60 Hz.
- Harmonic distortion, current: <3%.
- Distribution network type: TN and IT.
-
Efficiency:
- Maximum efficiency: 98.5%.
- Euro efficiency: 98.3% to 98.4%.
-
Power Consumption:
- Own consumption in operation: 1800 W.
- Standby operation consumption: 60 W.
- External auxiliary voltage: 400 V.
-
Dimensions and Weight:
- Width/Height/Depth: 4030 mm / 2150 mm / 720 mm.
- Weight: Approximately 3000 kg.
Environmental Limits:
- Degree of Protection: IP41.
- Ambient Temperature Range (nom. ratings): -20 to +50 °C.
- Maximum Ambient Temperature: +60 °C.
- Relative Humidity (non-condensing): 15 to 95%.
- Maximum Altitude (above sea level): 3000 m.
- Maximum Noise Level: <75 dBA.
- Maximum Air Flow: 10200 m³/h.
Protection:
- Ground fault monitoring.
- Grid monitoring.
- Anti-islanding.
- DC reverse polarity protection.
- AC and DC short circuit and over current protection.
- AC and DC over voltage and temperature protection.
User Interface and Communications:
- Local control panel.
- Analog inputs/outputs (extendable as an option).
- Digital inputs/relay outputs (extendable as an option).
- Fieldbus connectivity: Modbus, Profinet, Ethernet.
Product Compliance:
- Safety and EMC: CE conformity according to LV and EMC directives.
- Certifications and Approvals: CEA, CEI 0-16.
- Grid Support and Grid Functions: Reactive power compensation, FRT, Anti-islanding.
Additional Features:
- Cooling: Proven closed loop cooling system for demanding applications.
- Design: Fast and easy installation with integrated DC cabinet for space and cost savings.
- Maintenance: Low-maintenance cooling solution and robust protection for a service life of at least 20 years.
- Monitoring: Advanced grid support and monitoring features with remote control options.
- System Integrators: Versatile design enabling cost-effective multi-megawatt power plant setups.
Summary of PVS800-57B Central Inverter Models
Model | Maximum PV Power (PPV, max) | Maximum DC Current (Imax (DC)) | DC Voltage Range (mpp) | Maximum AC Power | Nominal Power (PN(AC)) | Nominal AC Current (IN(AC)) | Nominal Voltage (UN(AC)) | Efficiency (max) | Efficiency (Euro) |
---|---|---|---|---|---|---|---|---|---|
PVS800-57B-1645kW-C | 2468 kWp | 3700 A | 550 to 850 V | 1975 kW | 1645 kW | 2500 A | 380 V | 98.5% | 98.3% |
PVS800-57B-1732kW-C | 2598 kWp | 3700 A | 580 to 850 V | 2078 kW | 1732 kW | 2500 A | 400 V | 98.5% | 98.4% |